INSTALLATION & OPERATING INSTRUCTIONS

Below are the UL/ULC Listed instructions, for utilizing the E.V.S.

It’s a good idea to have the device instructions handy, so you can verify how the device is required to be installed with the EVS.

The EVS switch can do so much more, such as network systems, Buss, etc.

WIRING INSTALLATION LAYOUT

CONVENTIONAL END-OF-LINE RESISTOR CONNECTION DIAGRAM

TYPICAL (DCL) (SLC) ISOLATOR CONNECTION DIAGRAM

TYPICAL IN SUITE SOUNDER CONNECTION DIAGRAM

LOOP RESISTANCE CONNECTION DIAGRAM

FIX TEMPERATURE NON-RESTORABLE HEAT DETECTOR

SLC INPUT MONITORING MODULE INSTALLATION AND WIRING TESTING

SUPERVISORY / TROUBLE / ALARM / CONTACTS

CONTROL UNIT / ANNUNCIATOR

TYPICAL KITCHEN SUPPRESION CONNECTION DIAGRAM SUPERVISED-BY-PASSABLE (With new 4 wire microswitch)

TYPICAL KITCHEN SUPPRESION CONNECTION DIAGRAM (With old style 2 wire microswitch) (Not to be used for monitoring by-pass)

TYPICAL KITCHEN SUPPRESION CONNECTION DIAGRAM NON-BY-PASSABLE (With new 4 wire microswitch)

FIX TEMPERATURE NON-RESTORABLE HEAT DETECTOR (FT) INSTALLATION AND WIRING TEST (AS A JUMPER WIRE)

INSTALLATION & OPERATING INSTRUCTIONS

Thoroughly read and understand these Instructions, they provide detailed information on various applications. Copies are available from Offside Technologies Corp. These instructions are provided to ensure compliance with the Installation Requirements of NFPA-72 (National Fire Alarm Code), NFPA 70 (for US) and CSA C22.1, Canadian Electrical Code, Part 1, Safety Standard for Electrical Installations, Section 32- (for Canada), CAN/ULC-S524 (Standard for Installation of Fire Alarm Systems).  The Offside Technologies SM-001 is intended for permanent installation and can be used in lieu of any standard Fire Alarm System End-of-Line (EOL) device resistor plate. Or as an add on to: ISOLATOR DCL SLC / IN-SUITE SOUNDER / FIX TEMPERATURE HEAT / MONITORING MODULE / CONTROL UNIT (CU) / TRANSPONDER (T) /  ANNUNCIATORS / for ease of their respective testing requirements, that would otherwise require you to remove said device or wires from their respective backbox and/or terminal blocks for testing the wiring connected to said device.  A copy of these instructions should be left with the Building Fire Alarm System Verification Report.

The Offside Technologies SM-001 is compatible with most UL/ULC Listed Fire Alarm Control Panels, that do not exceed the ratings listed below.
In actual field testing it usually takes around 5 seconds or less to complete each test depending on the brand of Listed Fire Alarm System being used.
Terminals: R- R+ G – + are to be connected to Power-Limited circuits only.

IMPORTANT CAUTIONS

CANADIAN & USA APPLICATIONS:

An electrical backbox is required to be properly bonded to ground. Attach a ground wire to the designated ground terminal “G” and to the backbox for proper operation, where a ground condition is required. Follow published manufacture instructions for installed equipment for any extra requirements they have and the testing and maintenance instructions stipulated in CAN/ULC-S536 or NFPA 72 for USA, to ensure the proper utilization of the Offside Technologies SM-001. The Offside Technologies SM-001 is set for testing Positive Ground from the factory. If your codes require a Negative Ground as well as a Positive Ground for the same device e.g. CAN/ULC-S536-13, Section 6.2.2 “Control Unit or Transponder Tests” or if you want to achieve a Negative Ground only, you have three options;

(options 1) Use a test wire, not supplied:  From the front side of the mounting plate via the voltage/resistor measuring points while at “N” normal position, touch one end of the wire to the voltage point and the other end to either mounting screw.  Ensure non-painted mounting plate screws connect to the metal electrical box. This will ensure a ground reading can be achieved.

(options 2) Reverse connecting wires from + to for both voltage in and resistor out. This will put the power through the switch first. Allowing you to use the switch for testing Ground. The switch will provide same ratings in either + or configuration.

(options 3) Install two Offside Technologies SM-001 and connect one as normal and the other as option 2, reversing all wires.

RESISTOR , VOLTAGE & LOOP RESISTANCE MEASUREMENT

For testing the RESISTOR connected to the Offside Technologies SM-001 turn the switch to “O” open condition and insert your multi-meter set on (ohms) into the voltage/resistor measuring points on the front of the plate. You can now verify the resistor installed.

       For testing the VOLTAGE connected to the Offside Technologies SM-001 turn the switch to “N” and insert your multi-meter set on (Volts DC) into the voltage/resistor measuring points on the front of the plate. You can now verify the voltage.

      For testing the Loop Resistance; connect one SM-001 at the end of the wire loop, turn the switch to “S” and then use your multi-meter set on (ohms) at the beginning of the wire loop. Caution: You must remove power from the wire loop before you can verify the Loop Resistance. If you install a second SM-001 at the beginning, you can turn it to “O” and then insert probes into the measuring points and get your resistance reading. Figure D. Otherwise you need to remove wires from the control unit/transponder.

The device needs to be mounted onto a common single gang electrical box or adapter plate that is in accordance with the applicable Installation Standard, National Electrical Code, Electrical Code (both USA and Canada) and in accordance with the local authority having jurisdiction. Suitable for indoor dry locations only.

COMMON END-OF-LINE APPLICATION (EOL)

WARNING: Observe correct polarity when connecting wiring.
NOTE 1: Key-switch is in the “N” (normal circuit operation) position with the test key removed.
INSTALLATION: Reference Figure “A”.
NOTE 2: Use only resistor provided or specified by the fire control panel manufacturer. It is recommended to mount the Offside Technologies SM-001 less than 1800 mm above the floor (measured to the centre of the testing means) in order to facilitate easy access to the key-switch.
1. Connect the EOL resistor across “Resistor” (R- and R+) terminals of the SM-001 (Can be in either polarity in this application).
2. Connect field wiring from the control panel (or last device in the circuit) to terminals marked “” and “+” (observe polarity).
3. Connect a ground wire (not supplied) to the “G” terminal.
4. Install SM-001 with compatible hardware or hardware provided. Panel should indicate “normal” state when finished. If “off normal”, or “trouble” is indicated at the panel, check field wiring connections for zone in trouble.

Electrical Specifications

Voltage: 0 – 40 Vdc Operation
Rated Current: 0.1mA – 350mA
Temperature: 0°C to 49°C (32°F to 120°F)
Maximum Humidity: 93%. Noncondensing
Wire Gauge: 14 – 22 AWG
Max. Shorting Ckt. Current: 350mA

Abbreviation Meanings

“N” for “NORMAL OPERATION”
“O” for “OPEN CIRCUIT CONDITION”
“G” for “GROUND CONDITION”
“S” for “SHORT / ALARM CONDITION”

NOTE 3 WARNING: DO NOT sound the audible/strobe devices from any location while testing the audible/strobe EOL zones, while the EVS is in the “S” position. This will damage the key-switch. As the panel does not remove power from the audible/strobe  zones when in alarm state.

  1. Insert test key that came with the SM-001.
  2. Turn the key-switch from “N” position to “O”. This will display an “open circuit condition” at the control panel for that zone.
  3. Turn the key-switch to position “G”. This will cause the control panel to display “ground condition”, independent of the “open circuit condition”.
  4. Turn the key-switch to position “S”. This will impose a “short condition” on the zone. It will activate the “alarm condition” for initiating circuits and a “short fault condition” if connected to an output (NAC) circuit, independent of “O & G”.
  5. Return test key to “N” and remove.
  6. You can now measure voltage across the resistor by inserting a multi-meter, test probes into the & + probe holes provided on the face plate.
  7. For negative ground applications, for same device. See (options 2) above or insert test probe or ground wire into the “ “ hole provided and ground the other end of the probe/ground wire against one of the unpainted exposed screws used to secure the device to the electrical box. The control panels will indicate “Ground Condition” or “Trouble Condition” depending on brand of control panel.
  8. While in position “O” you can now measure your resistor value (ohms) across the test probe points. It is recommended to record all your readings.

WARNING: WHEN USING Offside Technologies Model SM-001 WITH: IN SUITE SOUNDER, BELL CIRCUIT, SPEAKER, or STROBE CIRCUITS. YOU ARE ONLY SHORTING THE ISOLATED SIDE. (See Note 3: above)

1. Insert the test key that came with the SM-001 into the 1st SM-001.
2. Turn the key to “O” position; this will cause an “open circuit condition” at the control panel. Now activate a drill test and confirm the in-suite sounder still operates.

  1. Turn the key to “G” position. This will cause a Ground Fault condition.
  2. Return the key to “N” position and remove the key.
  3. Now insert the test key into the 2nd SM-001 that has the jumper wire.
  4. Turn the key to “S” position. This will cause a “short” on the circuit which will be indicated as “short fault condition” or “NAC Fault” at the control panel.
  5. Now INITIATE an Alarm Test with the switch on “S” position, on the 2nd SM-001. The sounders associated with the suite to which the activated Offside Technologies SM-001 is connected should no longer function. All other in-suite sounders in the other suites on the floor area should continue to operate.
  6. Return test key to the “N” position. Sounders associated with the suite to which the device is connected should now commence sounding.
  7. Turn “off” the “Alarm Test” The control panel should return & read “normal operation”.
  8. Retest the in-suite sounder with the key removed, by activating manual “Alarm Test”. All in-suite sounders should operate as normal.

WARNING: Observe correct polarity when connecting wiring.

1. Insert the test key that came with the SM-001 switch on source side.
2. Turn the key to position “O”. (on the source side) This will cause the control panel’s loop controller to display an “Open Loop Fault” Once confirmed return key to “N” remove key.
3. If Field devices are connected insert test key on the second SM-001 isolated side and turn the key-switch to position “S”. This will cause the wiring to be shorted on the isolated side. Verify both isolator LED’S illuminate if LED’s are provided.
4. With the key maintained in “S” position, initiate the required testing for devices connected to the same loop controller on both the isolated and source sides confirm activation of a device before the source side of the floor area served by the isolator and confirm no activation of a device on the isolated side after the isolator.
5. Turn the key to the “N” position and remove the test key. All indications for the designated loop controller at the control panel should return to “normal” (A System Reset may be required)
6. If you need Ground Fault testing on the source side then turn the key-switch of the SM-001 on the source side to “G” confirm Ground, then return key to “N”.
7. If you need Ground Fault testing on the isolated side while testing the devices, turn the key to “G” on SM-001 on the isolated side confirm Ground Fault at the control unit or transponder. Then complete required testing to confirm connected fire alarm devices on the isolated side still function with the ground fault on.
8. To achieve a Negative ground fault follow option 3 and 2 above in “IMPORTANT CAUTIONS” and install another SM-001, for each. Repeat 6. & 7. Respectively. Then a “negative ground fault” condition should be indicated at the common control.
9. Turn the key to the “N” position and remove the test key. All indications for the designated loop controller at the control panel should read “normal”.

Breakaway Tabs

All four sides will breakaway if standard backboxes have been installed side by side. Simply use standard linemen’s pliers, place pliers up to the grove and bend back and forth along the whole line until it breaks off.

 

Figure C
CAUTION:
Maximum switching current is 350mA. Please ensure load calculations for the number of in-suite sounders connected to each Offside Technologies SM-001 do not exceed 350mA. For installations requiring more sounders, you may not be able to utilize the Offside Technologies SM-001 testing solution. For installations where current (including short circuit current) exceeds 350mA, you may not be able to utilize the Offside Technologies SM-001 testing solution.

Note 9: Install Offside Technologies SM-001 in accordance with the instructions. Mount units in close proximity to the in suite sounder isolator they serve and less than 1800mm above grade (to the centre of the plate).

COMMON IN SUITE SOUNDER ISOLATOR APPLICATION

WARNING: Must use correct polarity when connecting wiring.
NOTE 4: Normal circuit operation is with Key-switch in the “N” position and the test key removed.

INSTALLATION Reference Figure “C”.

  1. The Offside Technologies SM-001 should be mounted either adjacent to or below the in-suite signal isolator it will be testing. Two (2) SM-001 will be required, for each suite, the signalling isolator is monitoring. It is best to mount the SM-001 less than 1800mm above the floor for new installations or beside existing Isolator in retrofitting applications for ease of access to the key-switch.
    2. Connect one of the in-suite signal outputs from the isolator to the (“+” and “ – ”) terminals of the Offside Technologies SM-001. (Must use correct polarity)
    3. Connect the (R+ and R-) to the 2nd SM-001 ( “+” and “-“ ) then
    4. Connect the in-suite sounder to the (Resistor R+ and R-) of the 2nd SM-001 terminals of the device. (Must use correct polarity)
    5. Connect an output jumper wire for the 2nd SM-001 “+” to the R+. See figure C
    6. With the jumper wire installed, the 2nd SM-001 “O” position is not available on the device.
    7. Connect the return wires from the suite sounder to the applicable “return” terminals on the isolator. (Must use correct polarity)
    8. Connect the ground wire to 1st SM-001 (for Canadian Applications only).
    9. Install SM-001 with compatible hardware or hardware provided. Panel should indicate “normal” state when finished. If “off normal”, or “trouble” is indicated at the panel, check field wiring connections for zone in trouble.

Figure B – TYPICAL (DCL) (SLC) ISOLATOR CONNECTION DIAGRAM

Note 7: Install Offside Technologies SM-001 in close proximity to the (DCL) (SLC) isolator it serves and on a wall (where practical), less than 1800mm above grade (measured to the centre of the device).
Follow the instructions.

Note 8: Two Offside Technologies SM-001 are recommended for every (DCL) (SLC) isolated section in the circuit.

CAUTION: Maximum switching current is 350mA. Please ensure the load calculation for the number of active (or supporting) field devices connected to each Offside Technologies SM-001 does not exceed 350mA. For installations where current (including short circuit current) exceeds 350mA, you may not be able to utilize the Offside Technologies SM-001  testing solution.

 

DATA COMMUNICATION LINK OR SIGNALLING LINE CIRCUIT ISOLATOR APPLICATION (DCL) (SLC)

WARNING: Must use correct polarity when connecting wiring.
NOTE 5: Key-switch is in the “N” (normal circuit operation) position with the test key removed.

INSTALLATION Reference Figure “B”.

1. Two Offside Technologies SM-001 should be mounted either adjacent to or below the (DCL) (SLC) isolator it will be testing. For systems utilizing smoke detectors with isolator bases, locate SM-001 on an adjacent wall. It is best to mount the SM-001 less than 1800mm above the floor for new installations or beside existing isolator in retrofitting applications for ease of access to the key-switch.
2. The first one is connected on the source side (IN) of the isolator. Label it as such. Connect the input from the control unit/ transponder to the (“+” and “-”) terminals of Offside Technologies SM-001 (observe polarity). Then connect wires to the (RESISTOR R + and R –) terminals of the SM-001 unit (observe polarity) and then connect the wires back to the isolator + and inputs.
3. Connect the second SM-001 to the Isolated side (out) from the isolator (normally connected to the floor area devices) to the (“+” and “-”) terminals of Offside Technologies SM-001 (observe polarity). Label as such.
4. Connect the wiring for the field devices to the floor area to the (RESISTOR R + and R –) terminals of the SM-001 (observe polarity).
5. Connect an output jumper wire from the “+” to the R +. See figure B
6. With the jumper wire installed the “O” position is not available on the device.
7. Connect the ground to both SM-001 (may be used for both USA and Canada).
8. Install SM-001 with compatible hardware or hardware provided The loop controller should indicate a “normal condition”. If “off normal”, or
“trouble condition” is indicated for the circuit, check field wiring connection against instruction Figure B.

Figure A
NAC or Initiating Circuit from previous conventional field device.

CONVENTIONAL END-OF-LINE RESISTOR CONNECTION DIAGRAM

Note 6: Install Offside Technologies SM-001 in accordance with the instructions. Mount the SM-001 less than 1800mm above grade (to the centre of the plate). For retro fit installations confirm with AHJ that you can mount the SM-001 at higher locations. See ADDENDUM 001 for pole use.

CAUTION: Maximum switching current is 350mA.
Please ensure the load calculation for the number of active (or supporting) field devices connected to each Offside Technologies SM-001 does not exceed 350mA. For installations where current (including short circuit current) exceeds 350mA, you may not be able to utilize the Offside Technologies SM-001 testing solution.
Use only resistor provided or specified by the Fire Control Panel Manufacturer

LOOP RESISTANCE CONNECTION DIAGRAM

Figure D

Note 6: Install Offside Technologies SM-001 in accordance with the instructions. Mount units less than 1800mm above grade (to the centre of the plate).

CAUTION: Maximum switching current is 350mA. Please ensure the load calculation for the number of active (or supporting) field devices connected to each Offside Technologies SM-001 does not exceed 350mA. For installations where current (including short circuit current) exceeds 350mA, you may not be able to utilize the Offside Technologies SM-001 testing solution. Use only resistor provided or specified by the fire control panel manufacturer

 

See addendums for other applications

You may need to consult the AHJ to get approval for ADDENDUM applications, until the codes are updated to allow for alternative testing methods

The EVS is a UL & ULC listed device, some applications may require additional approval from AHJ. Existing codes were written with the technologies available at that time, they do not consider new and improved technologies. The AHJ is there to help all of us, improve fire protection. As in the Ontario Fire Code Part of the AHJ responsibilities are “to co-operate with any body or person interested in developing and promoting the principles and practices of fire protection services” and “to provide programs to improve practices relating to fire protection services.” All other Provinces or States most likely have a similar philosophy regarding improving fire protection.

The EVS is a vast improvement in various testing applications and as such we feel it is a better testing method than what is currently being done.

Drawings are TYPICAL they do not include every application. Prior to installing EVS, consult local fire codes as codes may vary from Province to Province or State to State.

FIX TEMPERATURE NON-RESTORABLE HEAT DETECTOR (FT) & SPRINKLER MONITORING SWITCHES (FS, LP, HP, SV,…) INSTALLATION AND WIRING TEST

This test only tests the wiring to a (FT) heat detector & Sprinkler monitoring switches. It does not test the actual heat detector or the mechanical part of the sprinkler monitoring switch itself. If the heat detector can be tested with a heat source without permanently damaging the detector, a heat source should be used to test the detector. Or if the Sprinkler Flow (FW) Low Pressure (LP) High Pressure (HP) Supervisory (SV) switch(s) the switches still need to be tested mechanically by a trained sprinkler technician during their inspection.

Addendum 001
To test a mechanical fixed non-restorable heat detector (FT), remove one positive and one negative wire from the detector on the power OUT, side of the detector. Connect those wires to the R+ & R- on the SM-001. Then connect a new wire going from the + of the SM-001 to the detector positive side. Then connect a new wire going from the – of the SM-001 to the detector negative side. The “G” terminal is not used for this test, but a ground wire still needs to be used from the detector backbox to the SM-001 backbox. Install the SM-001 at one of three locations: 1) beside the detector being tested and orientated so the testing key can be put on a key testing pole (sold separately) and access the SM-001 from VERTICALLY UNDERNEATH (NO OBSTRUCTIONS)

NOTE 10: the test key does not work on angle entry into the switch. 2) If you cannot access the detector directly from underneath, then you will have to move the SM-001 to a location that you can access it, from directly underneath.

Note 11: You will need to label the detector being tested with the same label put on or beside the SM-001 being used for testing that detector. 3) Install the SM-001 at no more than 1800mm from floor to give the best access point. You still must label the detector and the SM-001 so technicians know what the SM-001 is testing.

Note 12: If no label, then the SM-001 must be traced out to verify what it is testing and then relabel both devices. See example of label above. If this device is at the end of line then you can use the end of line as the test for the FT heat as well as the standard end of line. Label that it is doing both tests. For sprinkler switches follow the same steps in Addendum 001. Only trained sprinkler technicians are allowed to operate the sprinkler system. When installed correctly this will allow you to test the wiring integrity of the sprinkler monitoring switch(s).

To Test: Turn the test key straight to the “S” position to introduce a Short/Alarm condition. Return test key to “N” and remove test key. Test complete.

SLC INPUT MONITORING MODULE INSTALLATION AND WIRING TESTING (MM)

Addendum 002

Connect the + & wires coming from the Control Panel, to the SM-001 + & – . Then connect the R+ & R- of the SM-001 to the + &  IN of the MM. Then connect the desired devices to the + & – OUT of the MM. The G terminal is not used for this test, but a ground wire still needs to be used from backbox to backbox. You can now test the control panel’s ability to monitor the MM and all devices connected to it. To TEST: turn the key switch from “N” to “O”, the panel should show loss of communication to the MM address. Return the SM-001 to the “N” position. Test is complete. Note13: The last device connected to the MM has an EOL, install it in another SM-001 as per Figure A above.  Note 14: You will need to label what the SM-001 is testing. Put the same label on or beside the SM-001 and what is being tested. See Drawing #004 above. 

CONTROL UNIT / TRANSPONDERS / PRINTERS / ANNUNCIATOR / ALARM MONITORING / INSTALLATION AND TESTING

Addendum 003

All terminal screws and soldered terminal blocks over time wear out from use and when this happens you will have to replace the entire component. This could be the main mother board of the Control Board. To prevent this unnecessary wear from removing wires and terminal blocks: 1) Remove the wire to be tested and connect it to the R+ of the SM-001 add a new wire from the + of the SM-001 to what you just disconnected. Figure 003-1 This will turn the SM-001 into a wire break switch and you will never have to remove that wire again for testing. SPECIAL NOTE 15: Alarm monitoring of: Alarm; Trouble; Supervisory Contacts. Connect the SM-001 as shown in Figure 003-1 Drawing #006. Before turning to the “O” position, send signals to the monitoring station for each switch to confirm they are receiving signals. Once confirmed they have received the signals, turn the SM-001 to “O” this will bypass the monitoring. Once all your testing is done with the various devices return the key back to “N” normal position and remove the key. Then send one signal to the monitoring station for each monitoring contact to confirm the monitoring station is still receiving signals. Record the time they received the last signals.

Note 16: You may need to set up more than one SM-001 depending on the number of wires you are required to disconnect as per Code.
Note 17: Connect the Ground wire to G only when you want a ground condition as well.
Note 18: Connect the – wire only when you want + & – conditions, from the same source. See Figure 003-2
Note 19: For – Ground Conditions reverse the + & – so the SM-001 gives you a – Ground instead of a + Ground. You cannot get a + & a – Ground from one SM-001. There is a + & – probe on the faceplate that will allow + or – Ground, but it cannot be done by one key only.
Note 20: Label each SM-001 as to what it is doing. ( i.e.: Input wiring/circuit fault; monitoring circuit fault & – Ground; and or Output wiring circuit fault & + Ground)
To TEST: Simply turn the key from “N” to “O” to achieve the open condition test. Turn to “G” to get a positive ground test condition. Use option 2 or option 3 above to get your negative ground test condition. Turn the key switch to “S” if you need a short condition. Return the SM-001 to the “N” position, to return to a normal condition & remove test key.
NOTE 21: If the key is left in any SM-001 you can assume the system is not back to the normal state. All test keys MUST be removed upon completion of test for the system to be considered back to normal state.

ADDENDUM 004

CAUTION: Maximum switching current is 350mA. Please ensure the load calculation for the number of active (or supporting) field devices connected to each Offside Technologies SM-001 does not exceed 350mA. For installations where current (including short circuit current) exceeds 350mA, you may not be able to utilize the Offside Technologies SM-001 testing solution.

 

TYPICAL KITCHEN SUPPRESION CONNECTION DIAGRAM (With new 4 wire microswitch) DIAGRAM ALSO USED FOR SUPERVISED FIRE MONITORING CONTACTS

Note 21: If you want to use the SM-001 as a By-pass or test for when maintenance is being done on the Kitchen Suppression System or Fire Alarm Monitoring Contacts then you will need to install two SM-001 as per DRAWING #009
Follow the instructions.

Note 22: Joint annual inspection of suppression micro switch.
The suppression technician can turn the SM-001 #1 to the “O” position. This will put the Fire Panel in trouble only. Then the suppression technician can insert a multi-meter and when put on (ohms) can then activate the microswitch and confirm that the meter went to 0.00 confirming that the micro switch works. The technician marks on an inspection tag confirming that the microswitch went to 0.00. Then the Fire Alarm Technician completes the test of the SM-001 #2 during the annual test of the EOL.

Note 23: The Suppression technician will have to be shown by the fire alarm technician how the SM-001 work as a by-pass and how to get the )ohms) reading. If the suppression technician does not show they can correctly work a multi-meter, then joint coordination of the suppression and fire alarm test will have to be done at the same time.

COMMON KITCHEN SUPPRESSION BY-PASS APPLICATION (EOL) (4 wire microswitch) & FIRE MONITORING CONTACTS

WARNING: Observe correct polarity when connecting wiring.

NOTE 1: Key-switch is in the “N” (normal circuit operation) position with the test key removed.
INSTALLATION: Reference ADDENDUM 004, Drawing #009

NOTE 2:
Use only resistor provided or specified by the Fire or Monitoring Control Panel Manufacturer. It is recommended to mount the Offside Technologies SM-001 less than 1800 mm above the floor (measured to the centre of the testing means) in order to facilitate easy access to the key-switch.

1. Connect the EOL resistor across “Resistor” (R- and R+) terminals of the SM-001 #2 (Can be in either polarity in this application).
2. Connect a ground wire (not supplied) to the “G” terminal.
3. Connect one set of field wiring from the microswitch or monitoring contacts to terminals marked “-” and “+” of SM-001 #2 (observe polarity).
4. Connect one set of field wiring from the microswitch or monitoring contacts to terminals marked “R-” and “R+” of SM-001 #1 (observe polarity).
5. A ground wire is not needed at the “G” terminal for SM-001 #1. But the backbox still needs to be grounded.
6. Connect field wiring from the control panel to terminals marked “-” and “+” (observe polarity).
7. Install SM-001 with compatible hardware or hardware provided. Panel should indicate “normal” state when finished. If “off normal”, or “trouble” is indicated at the panel, check field wiring connections for zone in trouble.

RECOMMENDED TESTING PROCEDURE FOR KITCHEN SUPPRESSION BY-PASS; EOL & FIRE MONITORING CONTACTS

Kitchen Suppression Technician BY-PASS Instructions
1. Insert test key that came with the SM-001 #1.
2. Turn the key-switch from “N” position to “O” of SM-001 #1. This will display an “open circuit condition” at the control panel for that zone and by-pass the microswitch
3. Insert Multi-meter test probes into the voltage points of SM-001 #1 with your meter set to (ohms).
4. Activate the microswitch and the Multi-meter should read 0.00 (ohms). Record the date and reading on an inspection tag.
5. Return your microswitch to normal condition before doing step 6 or you will set off the fire alarm system.
6. Return test key of SM-001 #1 to “N” and remove. Return key back to the Fire Panel and Verify that the Fire Alarm panel has returned to normal condition.

Fire Alarm Technician Instructions for Kitchens.
1. Insert test key that came with the SM-001 #2.
2. Turn the key-switch from “N” position to “O” of SM-001 #2. This will display an “open circuit condition” at the control panel for that zone.
3. Turn the key-switch to position “G”. This will cause the control panel to display “ground condition”, independent of the “open circuit condition”.
4. Turn the key-switch to position “S”. This will impose a “short condition” on the zone. It will activate the “alarm condition” for initiating circuits and a “short fault condition” if connected to an output (NAC) circuit, independent of “O & G”.
5. Return test key to “N” and remove.
6. You can now measure voltage across the resistor by Inserting a multi-meter, test probes into the – & + probe holes provided on the face plate.
7. For negative ground applications, for same device. See (options 2) above or Insert test probe or ground wire into the “ – “ hole provided and ground the other end of the probe/ground wire against one of the unpainted exposed screws used to secure the device to the electrical box. The control panels will indicate “ground Condition” or “trouble condition” depending on brand of control panel.
8. While in position “O” you can now measure your resistor value (ohms) across the test probe points. It is Recommended to record all your readings.

Fire Alarm Technician Instructions for MONITORING CONTACTS.
1. Insert test key that came with the SM-001 #1.
2. Turn the key-switch from “N” position to “O” of SM-001 #1. This will display an “open circuit condition” at the monitoring station for that contact, it will also put the contact in by-pass mode from the fire panel till the key is returned to “N” position.
3. The monitoring station will no longer receive any more Troubles/Supervisory/Alarms from the fire panel for that contact/s till you return the key/s to the “N” position.
4. Return test key of SM-001 #1 to “N” and remove. Return key back to the Fire Panel and Verify that the monitoring station is still receiving singles by sending another test of the contact/s you were testing. Once confirmed by the monitoring station, then the contact/s have been returned to normal condition.

TYPICAL KITCHEN SUPPRESION CONNECTION DIAGRAM (With old style 2 wire microswitch) (Not to be used for monitoring by-pass)

Note 24: If you want to use the SM-001 as a By-pass for when maintenance is being done on the kitchen suppression system then you will need to install one SM-001 as per DRAWING #010
Follow the instructions.

Note 25: Joint annual inspection of suppression micro switch. The suppression technician can turn the SM-001 to the “O” position. This will put the Fire Panel in trouble only. Then the suppression technician can insert a multi-meter and when put on (ohms) can then activate the microswitch and confirm that the meter went to 0.00 confirming that the micro switch works. The technician marks on an inspection tag confirming that the microswitch went to 0.00. Then the Fire Alarm Technician completes the test during the annual test of the EOL.

Note 23: The Suppression technician will have to be shown by the fire alarm technician how the SM-001 work as a by-pass and how to get the (ohms) reading. If the suppression technician does not show that they can correctly work a multi meter, then joint coronation of the suppression and fire alarm test will have to be done at the same time.

Drawing #010 Revision 001

CAUTION: Maximum switching current is 350mA. Please ensure the load calculation for the number of active (or supporting) field devices connected to each Offside Technologies SM-001 does not exceed 350mA. For installations where current (including short circuit current) exceeds 350mA, you may not be able to utilize the Offside Technologies SM-001 testing solution.

COMMON KITCHEN SUPPRESSION BY-PASS APPLICATION (EOL) (2 wire microswitch)

WARNING: Observe correct polarity when connecting wiring.

NOTE 1: Key-switch is in the “N” (normal circuit operation) position with the test key removed.
INSTALLATION: Reference ADDENDUM 004, Drawing #010

NOTE 2: Use only resistor provided or specified by the fire control panel manufacturer. It is recommended to mount the Offside Technologies SM-001 less than 1800 mm above the floor (measured to the centre of the testing means) in order to facilitate easy access to the key-switch.

1. Connect the EOL resistor across “Resistor” (R- and R+) terminals of the SM-001 (Can be in either polarity in this application).
2. Connect a ground wire (not supplied) to the “G” terminal.
3. Connect field wiring from the microswitch to terminals marked “R -” and “R +” of SM-001 (observe polarity).
4. Connect field wiring from the control panel to terminals marked “-” and “+” (observe polarity).
5. Install SM-001 with compatible hardware or hardware provided. Panel should indicate “normal” state when finished. If “off normal”, or “trouble” is indicated at the panel, check field wiring connections for zone in trouble.

RECOMMENDED TESTING PROCEDURE FOR KITCHEN SUPPRESSION BY-PASS AND EOL (2 wire microswitch)

Kitchen Suppression Technician BY-PASS Instructions
1. Insert test key that came with the SM-001.
2. Turn the key-switch from “N” position to “O” of SM-001. This will display an “open circuit condition” at the control panel for that zone and by-pass the microswitch
3. Insert Multi-meter test probes into the voltage points of SM-001 with your meter set to OHMS.
4. Activate the microswitch and the Multi-meter should read 0.00 (ohms). Record the date and reading on an inspection tag.
5. Return your microswitch to normal condition before doing step 6 or you will set off the fire alarm system.
6. Return test key of SM-001 to “N” and remove. Return key back to the Fire Panel and Verify that the Fire Alarm panel has returned to normal condition.

Fire Alarm Technician Instructions.
1. Insert test key that came with the SM-001.
2. Turn the key-switch from “N” position to “O” of SM-001. This will display an “open circuit condition” at the control panel for that zone.
3. Turn the key-switch to position “G”. This will cause the control panel to display “ground condition”, independent of the “open circuit condition”.
4. Turn the key-switch to position “S”. This will impose a “short condition” on the zone. It will activate the “alarm condition” for initiating circuits and a “short fault condition” if connected to an output (NAC) circuit, independent of “O & G”.
5. Return test key to “N” and remove.
6. You can now measure voltage across the resistor by Inserting a multi-meter, test probes into the – & + probe holes provided on the face plate.
7. For negative ground applications, for same device. See (options 2) above or Insert test probe or ground wire into the “ – “ hole provided and ground the other end of the probe/ground wire against one of the unpainted exposed screws used to secure the device to the electrical box. The control panels will indicate “ground Condition” or “trouble condition” depending on brand of control panel.
8. While in position “O” you can now measure your resistor value (ohms) across the test probe points. It is Recommended to record all your readings.

TYPICAL KITCHEN SUPPRESION CONNECTION DIAGRAM NON-BY-PASSABLE (With new 4 wire microswitch)

Note 26: Standard installation of the SM-001 without being able to By-pass for when maintenance is being done on the kitchen suppression system install SM-001 as per DRAWING #011
Follow the instructions.

Note 27: Both technicians will be required at the same time to complete the annual inspection of suppression micro switch. Unless the fire alarm technician also has manufacture training on how to operate the suppression system.

In this configuration the SM-001 will not by-pass the microswitch.

CAUTION: Maximum switching current is 350mA. Please ensure the load calculation for the number of active (or supporting) field devices connected to each Offside Technologies SM-001 does not exceed 350mA. For installations where current (including short circuit current) exceeds 350mA, you may not be able to utilize the Offside Technologies SM-001 testing solution.

Drawing #011 Revision 001

COMMON KITCHEN SUPPRESSION NON-BY-PASS APPLICATION (EOL) (4 wire microswitch)

WARNING: Observe correct polarity when connecting wiring.

NOTE 1: Key-switch is in the “N” (normal circuit operation) position with the test key removed.
INSTALLATION: Reference ADDENDUM 004, Drawing #010

NOTE 2: Use only resistor provided or specified by the fire control panel manufacturer. It is recommended to mount the Offside Technologies SM-001 less than 1800 mm above the floor (measured to the centre of the testing means) in order to facilitate easy access to the key-switch.

1. Connect the EOL resistor across “Resistor” (R- and R+) terminals of the SM-001 (Can be in either polarity in this application).
2. Connect a ground wire (not supplied) to the “G” terminal.
3. Connect FIRST set of field wiring from the microswitch to terminals marked “-” and “+” of SM-001 (observe polarity).
4. Connect SECOND set of field wiring from the microswitch to the control panels + & (observe polarity).
5. Install SM-001 with compatible hardware or hardware provided. Panel should indicate “normal” state when finished. If “off normal”, or “trouble” is indicated at the panel, check field wiring connections for zone in trouble.

RECOMMENDED TESTING PROCEDURE FOR KITCHEN SUPPRESSION NON-BY-PASSABLE AND EOL (4 wire microswitch)

Fire Alarm Technician Instructions.
1. Insert test key that came with the SM-001.
2. Turn the key-switch from “N” position to “O” of SM-001. This will display an “open circuit condition” at the control panel for that zone.
3. Turn the key-switch to position “G”. This will cause the control panel to display “ground condition”, independent of the “open circuit condition”.
4. Turn the key-switch to position “S”. This will impose a “short condition” on the zone. It will activate the “alarm condition” for initiating circuits and a “short fault condition” if connected to an output (NAC) circuit, independent of “O & G”.
5. Return test key to “N” and remove.
6. You can now measure voltage across the resistor by Inserting a multi-meter, test probes into the – & + probe holes provided on the face plate.
7. For negative ground applications, for same device. See (options 2) above or Insert test probe or ground wire into the “ – “ hole provided and ground the other end of the probe/ground wire against one of the unpainted exposed screws used to secure the device to the electrical box. The control panels will indicate “ground Condition” or “trouble condition” depending on brand of control panel.
8. While in position “O” you can now measure your resistor value (ohms) across the test probe points. It is Recommended to record all your readings.

FIX TEMPERATURE NON-RESTORABLE HEAT DETECTOR (FT) INSTALLATION AND WIRING TEST (AS A JUMPER WIRE)

ADDENDUM 005

This test only tests the wiring to a (FT) heat detector. And does not test the actual heat detector itself. If the heat detector can be tested with a heat source without parentally damaging the detector, a heat source should be used to test the detector.

 

In ADDENDUM 005: To test a mechanical fixed non-restorable heat detector (FT), add one positive (JUMPER WIRE) and one negative (JUMPER WIRE) from the detector on the power IN, side of the detector. Connect those wires to the + & – on the SM-001. The “G” terminal is not used for this test, but a ground wire still needs to be used from the detector backbox to the SM-001 backbox.

In this configuration you have created a very long jumper wire depending on how far you install the SM-001 away from the FT. No wire resistance will be added to your loop for locations that are or are approaching the max allowed loop resistance for the zone you are working on. The test asks you to short the detector. So, there is very little difference if you short right at the detector or if you make your shorting wire long. The results are the same. You will need to get approval from your local AHJ as you are “T Tapping” but you are not adding any detection devices to the “T Tap” only the ability to test for short from a safe location.

Install the SM-001 at one of three locations: 1) beside the detector being tested and orientated so the testing key can be put on a key testing pole (sold separately) and access the SM-001 from VERTICALLY UNDERNEATH (NO OBSTRUCTIONS) NOTE 10: the test key does not work on angle entry into the switch. 2) If you cannot access the detector directly from underneath, then you will have to move the SM-001 to a location that you can access it, from directly underneath. Note 11: You will need to label the detector being tested with the same label put on or beside the SM-001 being used for testing that detector. 3) Install the SM-001 at no more than 1800mm from floor to give the best access point. You still must label the detector and the SM-001 so technicians know what the SM-001 is testing. Note 12: if no label then the SM-001 must be traced out to verify what it is testing and then relabel both devices. See example of label above. If this device is at the end of line, then you can use the end of line as the test for the FT heat as well as the standard end of line. Label that it is doing both tests.

To Test: Turn the test key straight to the “S” position to introduce a Short/Alarm condition. Return test key to “N” and remove test key. Test complete.

TYPICAL (DCL) (SLC) RELAY NORMALY OPEN CONNECTION DIAGRAM and testing of (DCL SLC) Relay without turning on Equipment

Addendum 006

Note 7: Install Offside Technologies SM-001 in close proximity to the (DCL) (SLC) Relay it serves and, on a wall, (where practical), less than 1800mm above grade (measured to the centre of the device).

Follow the instructions.

Note 28: Two Offside Technologies SM-001 are required for every (DCL) (SLC) Relay section in the circuit.

CAUTION:
CONTACT RATING 2.5amps @ Max 125 V AC.
350 mA @ 125 V DC Carry-3 AMPS continuous
Maximum switching current is 350mA. Please ensure the load calculation for the number of active (or supporting) field devices connected to each Offside Technologies SM-001 does not exceed 350mA. For installations where current (including short circuit current) exceeds 350mA, you may not be able to utilize the Offside Technologies SM-001 testing solution.

CAUTION:
NEVER connect a GROUND WIRE to the “G” of the SM-001 #02 when used with relays. You will short the power source to ground and may cause more damage than a tripped breaker.

You must consult your engineer prior to using addendum 006 or 007. Your engineer will verify if you will be exceeding any power limits of the SM-001 and verify if it will be compatible with your intended application. Warranty only applies if your engineer has stamped drawings that it can be used for your intended application.

If your code requires you to test for ground on the relay SOURCE SIDE, you can connect the ground wire. BUT NEVER ON THE RELAY SIDE!!!

TYPICAL INSTALATION OF (DCL) (SLC) RELAY NORMALY OPEN CONNECTION TESTING OF THE RELAY WITHOUT TURNING ON EQUIPMENT

WARNING: Observe correct polarity when connecting wiring. NEVER CONNECT A GROUND WIRE TO THE SM-001 # 02 “G” TERMINAL
NOTE 1: Key-switch is in the “N” (normal circuit operation) position with the test key removed.
INSTALLATION: Reference ADDENDUM 006, Drawing #013
NOTE 30: It is recommended to mount the SM-001 #01 on the source side of the Relay and SM-001 # 02 on the contact side. You however must label each as to what it is for and (Mark each i.e. Turn to “O” for test)

Step 1
1. Connect the Power Source negative – to the negative – of the Equipment it is to power (verify polarity in this application). Make your connections with the power off.
2. Connect the Power Source positive + to the “+” of the SM-001 # 02 (verify polarity in this application).
3. Connect a wire from the SM-001 # 02 “-” to the positive + of the Equipment you want the Fire Alarm Panel to be able to turn on (verify polarity in this application).
4. STOP NEVER ATTACH A GROUND WIRE (NOT SUPPLIED) TO THE “G” TERMINAL. (in this application) of the SM-001 # 02
5. Connect a wire from the SM-001 # 02 “R +” to the COM terminal of the Relay (observe polarity).
6. Connect a wire from the SM-001 # 02 “ R -” to the N/O terminal of the Relay (observe polarity).
7. Turn the power ON from the Power Source and Verify that the equipment is not working. If it is ON then your wiring is not correct.

Step 2
1. Turn off the power source to make the rest of your connections. Make your connections with the power off.
2. From the Control unit or Transponder connect the Power positive + of the (DCL SLC) to the “+” of the SM-001 # 01.
3. From the Control unit or Transponder connect the Power negative of the (DCL SLC) to the “-” of the SM-001 # 01.
4. From the SM-001 # 01 “ R + ” connect a wire to the (DCL SLC) Relay Positive + IN
5. From the SM-001 # 01 “ R – ” connect a wire to the (DCL SLC) Relay Negative – IN
6. Turn on power to the relay from the Control unit or Transponder and Power to equipment you are controlling if still off. The equipment should not be “ON” at this time. If it is re-check your wiring and or meter your relay contacts to see if your N/O is with power ON or with power OFF. You may need to reverse N/O & N/C depending on the brand of relay you are using.
Panel should indicate “normal” state when finished. If “off normal”, or “trouble” is indicated at the panel, check field wiring connections for zone in trouble.

TYPICAL TESTING OF (DCL) (SLC) RELAY NORMALY OPEN CONNECTION, TESTING OF THE RELAY WITHOUT TURNING ON EQUIPMENT

Step 1
1. Insert a testing key that came with the SM-001 # 01 into the SM-001 # 01.
2. Turn the key-switch from “N” position to “O” of SM-001 #01. This will display an “open circuit condition” at the control panel for the Relay. Record results.
3. Turn the key-switch back to “N” position and remove the key.

Step 2
1. Insert a testing key that came with the SM-001 # 02 into the SM-001 # 02.
2. Turn the key-switch from “N” position to “O” of SM-001 #02. This will by-pass any power from reaching the equipment you do not want to turn ON at this time.
3. Now insert the probes from your multi-meter into probe – and probe + on the face of the SM-001 # 02 and set it to OHMS. You should have and open reading (OL).
4. Now activate the Control unit or Transponder so that the Relay will switch from N/O to a closed contact state.
5. The multi-meter should now switch from reading open (OL) to reading closed (0.00). Thus, verifying that the Relay operates by the Control unit or Transponder.
6. Now reset the Control unit or Transponder so that the Relay returns to normal state. Your multi-meter will return to reading open (OL). Remove probes.
7. Turn the key-switch back to “N” position of the SM-001 # 02 and remove the key. Test complete record results.

Note 29: It is best practice that you allow the Fire Panel to do the full test without using the EVS once every two years encase some electrical work has been done but re-connected incorrectly.

TYPICAL (DCL) (SLC) RELAY NORMALY CLOSED CONNECTION DIAGRAM and testing of (DCL SLC) Relay without turning OFF Equipment

Addendum 007

Note 7: Install Offside Technologies SM-001 in close proximity to the (DCL) (SLC) Relay it serves and, on a wall, (where practical), less than 1800mm above grade (measured to the centre of the device).

Follow the instructions.

Note 28: Three Offside Technologies SM-001 are required for every (DCL) (SLC) Relay section in the circuit.

CAUTION:
CONTACT RATING 2.5amps @ Max 125 V AC.
350 mA @ 125 V DC Carry-3 AMPS continuous
Maximum switching current is 350mA. Please ensure the load calculation for the number of active (or supporting) field devices connected to each Offside Technologies SM-001 does not exceed 350mA. For installations where current (including short circuit current) exceeds 350mA, you may not be able to utilize the Offside Technologies SM-001 testing solution.

CAUTION:
NEVER connect a GROUND WIRE to the “G” of the SM-001 # 02 or SM-001 # 03 when used with relays. You will short the power source to ground and may cause more damage than a tripped breaker.

You must consult your engineer prior to using addendum 006 or 007. Your engineer will verify if you will be exceeding any power limits of the SM-001 and verify if it will be compatible with your intended application. Warranty only applies if your engineer has stamped drawings that it can be used for your intended application.

If your code requires you to test for ground on the relay SOURCE SIDE, you can connect the ground wire. BUT NEVER ON THE RELAY SIDE!!!

TYPICAL INSTALATION OF (DCL) (SLC) RELAY NORMALY CLOSED CONNECTION TESTING OF THE RELAY WITHOUT TURNING OFF EQUIPMENT

WARNING: Observe correct polarity when connecting wiring. NEVER CONNECT A GROUND WIRE TO THE SM-001 # 02 OR SM-001 # 03 “G” TERMINALS
NOTE 1: Key-switch is in the “N” (normal circuit operation) position with the test key removed.
INSTALLATION: Reference ADDENDUM 007, Drawing #014
NOTE 30: It is recommended to mount the SM-001 # 01 on the source side of the Relay and SM-001 # 02 & # 03 on the contact side. You however must label each as to what it is for and (Mark each i.e. Turn # 03 to “S” to keep power on to equipment; Turn # 02 to “O” to test Relay)

Step 1
1. Connect the Power Source negative – to the negative – of the Equipment it is to power (verify polarity in this application). Make your connections with the power off.
2. Connect the Power Source positive + to the “+” of the SM-001 # 03 (verify polarity in this application).
3. Connect a wire from the SM-001 # 03 “+“ to the positive “+” of the SM-001 # 02. (verify polarity in this application).
4. Connect a wire from the SM-001 # 02 “ R + ” to the COM terminal of the Relay (observe polarity).
5. STOP NEVER ATTACH A GROUND WIRE (NOT SUPPLIED) TO THE “G” TERMINAL. (in this application) of the SM-001 # 02 or # 03
6. From the Equipment you want to keep ON Connect a wire from the + terminal to the Relay “ N/C ” (observe polarity).
7. Turn the power ON from the Power Source and Verify that the equipment is working. If it is OFF then your wiring is not correct. Or your Relay has to have power going to it first to operate as N/C.

Step 2
1. Turn off the power source to make the rest of your connections. Make your connections with the power off.
2. From the Control unit or Transponder connect the Power positive + to the “+” of the SM-001 # 01.
3. From the Control unit or Transponder connect the Power negative to the “-” of the SM-001 # 01.
4. From the SM-001 # 01 “ R + ” connect a wire to the (DCL SLC) Relay Positive + IN
5. From the SM-001 # 01 “ R – ” connect a wire to the (DCL SLC) Relay Negative – IN
6.Turn on power to the relay from the Control unit or Transponder and Power to the equipment you are controlling. The equipment should be “ON” at this time. If it is not re-check your wiring and or meter your relay contacts to see if your N/C is with power ON or with power OFF. You may need to reverse N/C & N/O depending on the brand of relay you are using.

Panel should indicate “normal” state when finished. If “off normal”, or “trouble” is indicated at the panel, check field wiring connections for zone in trouble.

TYPICAL TESTING OF (DCL) (SLC) RELAY NORMALY CLOSED CONNECTION, TESTING OF THE RELAY WITHOUT TURNING OFF EQUIPMENT

Step 1
1. Insert a testing key that came with the SM-001 # 01 into the SM-001 # 01.
2. Turn the key-switch from “N” position to “O” of SM-001 # 01. This will display an “open circuit condition” at the control panel for the Relay. Record results.
3. Turn the key-switch back to “N” position and remove the key.

Step 2
1. Insert a testing key that came with the SM-001 # 03 into the SM-001 # 03.
2. Turn the key-switch from “N” position to “S” of SM-001 # 03. This will MAINTAIN power TO the equipment you do not want to turn OFF. Leave key set to “S” for now.

Step 3
1. Insert a testing key that came with the SM-001 # 02 into the SM-001 # 02.
2. Caution do not turn SM-001 # 02 to “O” position unless you have first turned SM-001 # 03 to “S” position IN STEP 2 or you will turn OFF the equipment you do not want to turn off. Now turn the key-switch from “N” position to “O” of SM-001 #02. This will by-pass power going from the Relay to the equipment you do not want to turn OFF. (as long as step 2 is set to “S” power is going to the equipment via SM-001 # 03 by-pass)

Step 4
1. Now with your multi-meter set to Volts insert your + test probe into the + probe hole of the SM-001 # 02 and place the other – probe of your multi-meter to the mounting screw that secures the SM-001 # 02 to the backbox (Your backbox must be grounded to ground) You should now have a reading of the voltage of the equipment that is running through the Relay. Record the reading. _____ A/C or DC It cannot exceed 125 volts.
2. Now turn the test key of the SM-001 # 02 from “N” to “O” and the voltage should go to 0.00 Volts. Confirming that power is removed from the Relay N/C side.

Step 5
1. Now set your multi-meter to OHMS insert one test probe into the – probe of the SM-001 # 03 and place the other + probe into the + of the SM-001 # 02. You should have and open reading (OL).
2. Now activate the Control unit or Transponder so that the Relay will switch from N/C to an OPEN contact state. Your multi-meter will change from closed to open. This verifies that your relay operates. Record the results.
3. Now reset the Control unit or Transponder so that the Relay returns to normal state. Your multi-meter will return to reading closed (0.00). Remove probes. If it does not your relay is not reset. Correct the problem before going to Step 6. Or you may turn off power to your equipment.

Step 6
1. Return the key switch of the SM-001 # 02 to “N” normal state FIRST and remove the test key.
2. Next Return the key switch of the SM-001 # 03 to “N” normal state and remove the test key. Your test is complete. Verify that your equipment is still in operation.

Note 29: It is best practice that you allow the Fire Panel to do the full test without using the EVS once every two years encase some electrical work has been done but re-connected incorrectly.

CAUTION

If beginning construction/repairs/maintenance where water/dust producing activities could cause damage to the SM-001 key-switch and or measuring points, Offside Technologies Corp. recommends placing a protective covering (not supplied) over the SM-001 or removal before work is done. Temporary protective caps are available through Offside Technologies Corp. The caps can be an effective way to limit the entry of water & dust into the key-switch & voltage/resistor measuring points. However, they may not completely prevent water or dust particles from entering the key-switch & measuring points and have not been tested with UL for this application.

Five-Year Limited Warranty
Offside Technologies Corp. warrants the enclosed Electronic Verifying Switch model SM-001 to be free from defects in materials and workmanship under normal service and use for a period of five years from date of manufacture. Offside Technologies Corp. makes no other express warranty for this Electronic Verifying Switch model SM-001. No employee, dealer, or agent representative, of the Company has the authority to alter the obligations or limitations of this Warranty. Offside Technologies Corp’s obligation for this Warranty shall be limited to the replacement of any part of the Electronic Verifying Switch model SM-001 which is found to be defective in materials or workmanship under normal use and service during the five year period commencing with the date of manufacture. Please phone Offside Technologies Corp. 1-905-903-5688 for a Return Authorization Number. Then send the defective unit(s) postage prepaid to: Offside Technologies Corp., C/O Repairs, 717 Wilson Road South Unit 5 Oshawa, Ontario, Canada L1H 6E9. (Include Return Authorization Number_ _ _ _) along with: A note describing the malfunction and location of building it was installed in. A copy of the installation and Verification Report for when the device was installed. The Company shall not be obligated to replace units which are found to be defective because of dam¬age, unreasonable use, modifications, or alterations occurring after the date of manufacture. In no case shall Offside Technologies Corp. be liable for any consequential or incidental damages for breach of this or any other Warranty, expressed or implied whatsoever, even if the loss or damage is caused by Offside Technologies Corp. negligence or fault. This Warranty gives you specific legal rights, and you may also have other rights under common law.

MANUFACTURERS INFO

Manufactured in Canada by: Offside Technologies Corp.

Manufacturing Location
717 Wilson Road South Unit 5, Oshawa, ON   L1H 6E9
Email: mark@offsidetechnologies.com
Tel: 905-409-2751

Distributer
717 Wilson Road South Unit 5, Oshawa, ON L1H 6E9
Email: stephen@offsidetechnologies.com
Tel: 905-903-5688

AGENCY LISTINGS

E.V.S. A TRUE TIME SAVING DEVICE

Install Electronic Verifying Switches (E.V.S.) today!
Contact us for purchasing details.

mark@offsidetechnologies.com
905-409-2751

stephen@offsidetechnologies.com
905-903-5688